CPU304
●K304-14AT
●K304-14AR
●K304-14AX
- Detaylar
Model | K304-14AT K304 K304-14AR K304-14AX | |||
CPU | 16-Bit Industrial | |||
Execution Speed | Typical Bool Instruction Time: <1μS | |||
Word Operation Time: <96μS | ||||
Arithmetic Operation Time for Integers: <130μS | ||||
Arithmetic Operation Time for Floating Points: <300μS | ||||
DI Points | 8XDC24V | |||
DO Points | 6XDC24V | 6XRelay | 3XDC24V+3XRelay | |
User Program Memory | EEPROM, 8KB | |||
Program Backup | Permanent Storage, Without the Need of Battery//1000 Instructions | |||
Memory Area | Variable Storage Area (V Area): 2KB | |||
System Storage Area (SM Area): 300 Bytes | ||||
Internal Storage Area (M Area): 32 Bytes | ||||
Data Retention Characteristic | Configure with the Programming Software: V Area, C (Counter) Area | |||
Retention Mode and Period | Adopt super capacitors and support a retention period of not less than 144 hours upon power failure under normal temperature. | |||
Data Backup Characteristic | Perform Backup Operations VB1648 ~ VB1775 According to User Instructions, 128 Bytes in Total | |||
Backup Mode and Time | EEPROM (Writing Operation for 1 Million Times) Permanent Backup | |||
Floating Points | Supported; the Whole V Area can be Used for Floating Points | |||
Programming Language Supported | Ladder Drawing (LD), Instruction List (IL) | |||
Instruction Set | Basic Instructions: 55; Expansion Instructions: 251 | |||
Password | Yes | |||
Protection | ||||
Digital Data: 14 in Total (DI8, DO6); | ||||
Analog Data: None | ||||
Counter | 64 | |||
Operation Mode of Counter | Addition, Subtraction | |||
Counter Range | -32768~32767 | |||
Counting Value Retention Function | Yes | |||
64 | ||||
1 ms time Base: 4 | ||||
10 ms Time Base: 16 | ||||
100 ms Time Base: 44 | ||||
2 Single/Dual-Phase High-Speed Counters | ||||
Where, Single-Phase Counter with a Maximum Frequency of 20KHz | ||||
Dual-Phase Counter with a Maximum Frequency of 10KHz | ||||
2, PTO (Pulse Train Output)/PWM (Pulse Width Modulation Output); | ||||
Maximum Output Frequency: 20 KHz | ||||
Analog Potentiometer | - | |||
Timing Interruption: 2, 1ms Resolution; | ||||
Timer Interruption: T2/T3, 1ms Resolution; | ||||
Edge Interruption: 4, Rising Edge or Falling Edge Optional; | ||||
High-Speed Interruption, Communication Interruption | ||||
- | ||||
Number of Connectable Expansion Modules | - | |||
COM Port | 1, RS232 or RS485; | |||
Supported Working Modes: Programming, Modbus-RTU (Slave), Free Protocol | ||||
Equipment Connected with COM Port | RS232/RS485: PC (For Programming), Third-Party HMI Panel, Third-Party Serial Communication Equipment (For Example, Instruments, Bar Code Reader, etc.) | |||
Input Power Supply | AC85~265V | |||
Sensor Load Power Supply | DC24V, Max. 300 mA | |||
Dimensions (L*W*H) | 97X114X70mm |